Why a battery can run a fridge but fail to start it
Stored energy, continuous AC output and motor startup capability are independent limits.
The compressor start is brief but demanding
The steady running watts and the first moments of motor startup are different loads. If a label provides locked-rotor current, it describes a specific electrical condition and is not the same as average consumption.
Boost features are not motor-start proof
Some stations support higher advertised wattage by reducing voltage for resistive appliances. That is not equivalent to preserving normal voltage during a compressor start. This planner leaves unverified surge ratings for a manual check.
Use measured and documented inputs
Find the appliance and station manuals, use a suitable meter and test the exact combination. Schedule large resistive loads away from compressor starts when possible, but do not assume software will always prevent overlap.
Energy, running power and startup: three checks
Here is a hypothetical fridge with 120 W running draw, a 25% duty cycle and a 900 W startup requirement. Use measured or documented values for your own appliance.
| Check | Example requirement | Compare against |
|---|---|---|
| Daily energy | 120 × 24 × 0.25 = 720 Wh | Usable capacity plus losses |
| Running output with a 10 W router | 120 + 10 = 130 W | Continuous AC output |
| Startup with the router still on | 900 + 10 = 910 W | Documented startup capability |
A station can pass the 130 W running check and still fail the 910 W startup check. The planner assumes one motor starts while other scheduled loads run. Surge duration, voltage behaviour and multiple simultaneous starts need the exact manuals and a real test.
Before choosing your setup
- Keep the compressor’s active watts separate from its daily average.
- If you enter measured daily-average watts, set duty cycle to 100% to avoid counting cycling twice.
- Treat an unknown surge rating as a manual check, even if the battery capacity fits.
Common questions
Should I multiply startup watts by 24 hours?
No. Startup is brief and is checked as a power demand. Daily energy depends on the operating draw and cycling time, not a full day at startup power.
Does a boost mode prove the fridge will start?
No. Some boost modes reduce voltage for resistive loads. Check true motor-start capability and test the exact fridge and station combination.
This guide explains electrical planning for portable plug-in devices. Verify your exact manufacturer manuals and operating conditions.